;0x1200 Modbus通用测试用 [comm] debug=1 ;打开调试输出信息 默认0(不打开) delay=500 ;采集指令延时,单位 ms 默认10 mask=0 ;保留 model=OM-MDBS4938 ;型号 添加支持类型用 note=精密空调; 山特SCC空调MODBUS通讯协议-V1.1(轴流及25-100kw)(1).pdf brief=室内温度: %1% ℃ %1st%,室内湿度: %2% % %2st%;简报 %x%为某字段值 简报中不能带分号; [regs1] 8001=1;室内机组状态 8017=40; 8104=10;室外机1组状态 [regs3] 8001=15;室内机组模拟量 8001bit=1 8101=4;室外机组1模拟量 [flds] cnt=30 1=48006;室内温度 2=48007;室内湿度 3=48015;电源电压 4=48002-0;B0:制冷; 5=48002-1;B1:制热; 6=48002-2;B2:加湿; 7=48002-3;B3:除湿; 8=08002;开/关状态 9=08018; 电源故障 10=08019; 相序错误 11=08020; 缺相错误 12=08021; 电加热保护 13=08022; 加湿器报警 14=08033; 滤网堵塞报警 15=08042; 风机过载故障 16=08044; 高温报警 17=08045; 低温报警 18=08046; 高湿报警 19=08047; 低湿报警 20=08050; 回风温度探头1故障 21=08051; 回风温度探头2故障 22=08052; 回风温度探头3故障 23=08053; 回风湿度探头故障 25=08106; 室外温度传感器故障 26=08107; 压力传感器故障 27=08108; 系统高压保护 28=08109; 系统低压保护 29=08113; 变频驱动故障 30=08114; 风机过热保护 [flds.def] ;x=FldName,FldDept,Note,vkind,vfactor,vmode,vref,vtip,vref2,vtip2 1='Fld',1,'室内温度',0,10,11,250,'最小值|允许最低值',350,'最大值|允许最高值' 2='Fld',1,'室内湿度',0,10,11,10,'最小值|允许最低值',750,'最大值|允许最高值' 3='Fld',1,'电源电压',0,1,11,0,'最小值|允许最低值',250,'最大值|允许最高值' 4='Fld',1,'制冷',0,1,0,0,'0:关,1:开',0,'' 5='Fld',1,'制热',0,1,0,0,'0:关,1:开',0,'' 6='Fld',1,'加湿',0,1,0,0,'0:关,1:开',0,'' 7='Fld',1,'除湿',0,1,0,0,'0:关,1:开',0,'' 8='Fld',1,'开/关机状态',0,1,0,0,'0:关机,1:开机',0,'' 9='Fld',1,'电源故障',0,1,0,0,'0:正常,1:故障',0,'' 10='Fld',1,'相序错误',0,1,0,0,'0:正常,1:告警',0,'' 11='Fld',1,'缺相错误',0,1,0,0,'0:正常,1:告警',0,'' 12='Fld',1,'电加热保护',0,1,0,0,'0:正常,1:告警',0,'' 13='Fld',1,'加湿器报警',0,1,0,0,'0:正常,1:告警',0,'' 14='Fld',1,'滤网堵塞报警',0,1,0,0,'0:正常,1:告警',0,'' 15='Fld',1,'风机过载故障',0,1,0,0,'0:正常,1:故障',0,'' 16='Fld',1,'高温报警',0,1,0,0,'0:正常,1:告警',0,'' 17='Fld',1,'低温报警',0,1,0,0,'0:正常,1:告警',0,'' 18='Fld',1,'高湿报警',0,1,0,0,'0:正常,1:告警',0,'' 19='Fld',1,'低湿报警',0,1,0,0,'0:正常,1:告警',0,'' 20='Fld',1,'回风温度探头1故障',0,1,0,0,'0:正常,1:故障',0,'' 21='Fld',1,'回风温度探头2故障',0,1,0,0,'0:正常,1:故障',0,'' 22='Fld',1,'回风温度探头3故障',0,1,0,0,'0:正常,1:故障',0,'' 23='Fld',1,'回风湿度探头故障',0,1,0,0,'0:正常,1:故障',0,'' 25='Fld',1,'室外温度传感器故障',0,1,0,0,'0:正常,1:故障',0,'' 26='Fld',1,'压力传感器故障',0,1,0,0,'0:正常,1:故障',0,'' 27='Fld',1,'系统高压保护',0,1,0,0,'0:正常,1:告警',0,'' 28='Fld',1,'系统低压保护',0,1,0,0,'0:正常,1:告警',0,'' 29='Fld',1,'变频驱动故障',0,1,0,0,'0:正常,1:故障',0,'' 30='Fld',1,'风机过热保护',0,1,0,0,'0:正常,1:告警',0,''