;0x1200 Modbus通用测试用 [comm] debug=1 ;打开调试输出信息 默认0(不打开) delay=50 ;采集指令延时,单位 ms 默认10 mask=0 ;保留 model=OM-MDBS4936 ;型号 添加支持类型用 note=精密空调; 说明 科士达空调 brief=回风温度: %1% ℃, 回风湿度: %2% % ;简报 %x%为某字段值 简报中不能带分号; Yk00=05274EFFFF ;开机模式 Yk01=05274E0000 ;关机模式 Yk04=067551 ;设置温度 Yk05=067554 ;设置湿度 [regs1] 10029=2 10033=1 10055=4 10085=1 10087=1 10089=1 10091=1 10097=1 10101=6 10133=3 10080=5 10093=1 10095=1 10099=2 10142=2 [regs3] 30001=2 30061=1 30033=1 30036=1 [flds] cnt=36 1=430002 2=430003 3=430062 4=010030 5=010031 6=010034 7=010056 8=010057 9=010058 10=010059 11=010086 12=010088 13=010090 14=010092 15=010098 16=010102 17=010103 18=010104 19=010105 20=010106 21=010107 22=010134 23=010136 24=010081 25=010082 26=010083 27=010084 28=010085 29=010094 30=010096 31=010100 32=010101 33=010143 34=010144 35=430034 36=430037 [flds.def] ;x=FldName,FldDept,Note,vkind,vfactor,vmode,vref,vtip,vref2,vtip2 1='Fld',1,'回风温度',0,10,11,150,'最小值|允许最低值',350,'最大值|允许最高值' 2='Fld',1,'回风湿度',0,10,11,300,'最小值|允许最低值',750,'最大值|允许最高值' 3='Fld',1,'运行状态',0,1,0,0,'0:关机,1:运行,2:待机,3:锁定,4:远程关机',0,'' 4='Fld',1,'压缩机1',0,1,0,0,'0:关闭,1:开启',0,'' 5='Fld',1,'压缩机2',0,1,0,0,'0:关闭,1:开启',0,'' 6='Fld',1,'加湿器',0,1,0,0,'0:关闭,1:开启',0,'' 7='Fld',1,'制冷',0,1,0,0,'0:关闭,1:开启',0,'' 8='Fld',1,'加热',0,1,0,0,'0:关闭,1:开启',0,'' 9='Fld',1,'加湿',0,1,0,0,'0:关闭,1:开启',0,'' 10='Fld',1,'除湿',0,1,0,0,'0:关闭,1:开启',0,'' 11='Fld',1,'压缩机1高压',0,1,0,0,'0:正常,1:告警',0,'' 12='Fld',1,'压缩机2高压',0,1,0,0,'0:正常,1:告警',0,'' 13='Fld',1,'压缩机1低压',0,1,0,0,'0:正常,1:告警',0,'' 14='Fld',1,'压缩机2低压',0,1,0,0,'0:正常,1:告警',0,'' 15='Fld',1,'室内风机',0,1,0,0,'0:正常,1:告警',0,'' 16='Fld',1,'加湿器',0,1,0,0,'0:正常,1:告警',0,'' 17='Fld',1,'电加热器',0,1,0,0,'0:正常,1:告警',0,'' 18='Fld',1,'送风湿感',0,1,0,0,'0:正常,1:告警',0,'' 19='Fld',1,'送风温感',0,1,0,0,'0:正常,1:告警',0,'' 20='Fld',1,'回风温感',0,1,0,0,'0:正常,1:告警',0,'' 21='Fld',1,'回风湿感',0,1,0,0,'0:正常,1:告警',0,'' 22='Fld',1,'烟火',0,1,0,0,'0:正常,1:告警',0,'' 23='Fld',1,'电源',0,1,0,0,'0:正常,1:告警',0,'' 24='Fld',1,'漏水',0,1,0,0,'0:正常,1:告警',0,'' 25='Fld',1,'高温',0,1,0,0,'0:正常,1:告警',0,'' 26='Fld',1,'低温',0,1,0,0,'0:正常,1:告警',0,'' 27='Fld',1,'高湿',0,1,0,0,'0:正常,1:告警',0,'' 28='Fld',1,'低湿',0,1,0,0,'0:正常,1:告警',0,'' 29='Fld',1,'压缩机1排气',0,1,0,0,'0:正常,1:告警',0,'' 30='Fld',1,'压缩机2排气',0,1,0,0,'0:正常,1:告警',0,'' 31='Fld',1,'气流丢失',0,1,0,0,'0:正常,1:告警',0,'' 32='Fld',1,'滤网脏堵',0,1,0,0,'0:正常,1:告警',0,'' 33='Fld',1,'室外机1风机',0,1,0,0,'0:正常,1:告警',0,'' 34='Fld',1,'室外机2风机',0,1,0,0,'0:正常,1:告警',0,''